3.8.8 39(0x27) Set Power-on Value
This sub-function code is used to set the power-on
value of a module.
Request
00
Address
01
Function code
02
Sub-Function code
03
Power-on Value
04
Power-on Value
05
Power-on Value
06
Power-on Value
Response:
00
Address
01
Function code
02
Sub-Function code
03
Power-on Value
Error Response:
00
Address
01
Function code
02
Exception code
M-7065 User's Manual Ver2.0, Dec. /200 8 ---131
1 Byte
1 Byte
1 Byte
1 Byte
0x00-0xFF (DOI0-DO7)
1 Byte
0x00-0xFF (DO8-DO15)
1 Byte
0x00-0xFF (DO16-DO23)
1 Byte
0x00-0xFF (DO24-DO31)
1 Byte
1 Byte
1 Byte
0 : OK
1 Byte
Others : Error
1 Byte
1 Byte
Refer to Modbus standard
1 Byte
for more details
1-247
0x46
0x27
1-247
0x46
0x27
1-247
0xC6