There will be no response if the command syntax is
incorrect, there is a communication error, or there is
no module with the specified address.
Examples:
Command:@016
Response:>
Sets DO1、2 to on、DO0、3 to off.
Command:$01C
Response:!01
Sends the command to clear the status of the
latched digital input channels of module 01 and
returns a valid response.
Command:$01L0
Response:!093F00
Sends the command to read the status of the low
latched digital input channels of module 01.
Low Latched DI : 0x3F
Low Latched DO : 0x09