3.8.3 05(0x05) Read Communication
This sub-function code is used to read the
communication protocol settings of a module
Request
00
Address
01
Function code
02
Sub-Function code
03
Reserved
Response:
00
Address
01
Function code
02
Sub-Function code
03
Protocol support
04
Baud Rate
05
Reserved
06
Parity
07
Reserved
08
Protocol Mode
09-10
Reserved
M-7065 User's Manual Ver2.0, Dec. /200 8 ---122
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
0 ,1 : Modbus RTU
1 Byte
3 : Modbus RTU/ASCII
1 Byte
1 Byte
0 : N81
1 : N82
1 Byte
2 : E81
3 : O81
1 Byte
0 : DCON
1 Byte
1 : Modbus RTU
3 : Modbus ASCII
2 Byte
1-247
0x46
0x05
0x00
1-247
0x46
0x05
0x0A
0x00
0x00
0x00 0x00