3.5 05(0x05) Write single coils

This function code is used to write the digital
output value.
Request
00
Address
01
Function code
Output channel
02-03
numbers
04-05
Output value
M-7065 User's Manual Ver2.0, Dec. /200 8 ---110
1 Byte
1 Byte
DO : 0x0000-0x001F
Clear DI count value :
0x0200-0x021F
Safe Value :
0x0080-0x009F
Power On Value :
2 Byte
0x00A0-0x00BF
Clear Latched : 0x0107
Set WDT Mode : 0x0103
Set WDT Enable :
0x0104
Clear WDT Status :
0x010D
A value 0xFF00 sets the
output to ON
2 Byte
A value 0xFF00 sets the
output to OFF