0X00) Read Module Name - ICP DAS USA M-7065 User Manual

Data acquisiton and control modules
Table of Contents

Advertisement

3.8.1 00(0x00) Read Module Name

This sub-function code is used to read the name of
a module.
Request
00
Address
01
Function code
02
Sub-Function code
Response:
00
Address
01
Function code
02
Sub-Function code
03-06
Module name
Error Response:
00
Address
01
Function code
02
Exception code
Examples:
Command:05 46 00 [ 53 A1 ]
Response:05 46 00 00 70 65 00 6A 2D
M-7065 User's Manual Ver2.0, Dec. /200 8 ---120
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
0x00 0x70 0x65 0x00 for
4 Byte
1 Byte
1 Byte
Refer to Modbus standard
1 Byte
for more details
1-247
0x46
0x00
1-247
0x46
0x00
M-7065
1-247
0xC6

Advertisement

Table of Contents
loading

Table of Contents