X06) Set Communication - ICP DAS USA M-7065 User Manual

Data acquisiton and control modules
Table of Contents

Advertisement

3.8.4 06(0x06) Set Communication

This sub-function code is used to set the
communication protocol of a module.
Request
00
Address
01
Function code
02
Sub-Function code
03
Reserved
04
Baud Rate
05
Reserved
06
Parity
07
Reserved
08
Protocol Mode
09-10
Reserved
Response:
00
Address
01
Function code
02
Sub-Function code
03
Reserved
04
Baud Rate
M-7065 User's Manual Ver2.0, Dec. /200 8 ---124
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
0 : N81
1 : N82
1 Byte
2 : E81
3 : O81
1 Byte
0 : DCON
1 Byte
1 : Modbus RTU
3 : Modbus ASCII
2 Byte
1 Byte
1 Byte
1 Byte
1 Byte
1 Byte
0 : OK
1-247
0x46
0x06
0x00
0x0A
0x00
0x00
0x00 0x00
1-247
0x46
0x06
0x00

Advertisement

Table of Contents
loading