Aa0A(Data) - ICP DAS USA M-7065 User Manual

Data acquisiton and control modules
Table of Contents

Advertisement

2.4 #AA0A(Data)

Description:
Sets the digital output value.(DO0-DO31)
Syntax:
#AA0A(Data)[CHKSUM](CR)
#
Delimiter character
AA
Address of the module to be set (00 to FF)
0A
Command to set the digital output value.
(DO0-DO31)
#AA0A(Data) : DO0-DO7
#AA0B(Data) : DO8-DO15
#AA0C(Data) : DO16-DO23
#AA0D(Data) : DO24-DO31
(Data)
A two-digit hexadecimal value, where bit 0
corresponds to DO0, bit 1 corresponds to
DO1, etc. When the bit is 1, it denotes that
the digital output channel is on, and 0
denotes that the digital output channel is off.
M-7065 User's Manual Ver2.0, Dec. /200 8 ---29