Aao(Name) - ICP DAS USA M-7065 User Manual

Data acquisiton and control modules
Table of Contents

Advertisement

2.21 ~AAO(Name)

Description:
Sets the name of a module.
Syntax:
~AAO(Name) [CHKSUM](CR)
~
Delimiter character
AA
Address of the module to be set (00 to FF)
O
Command to set the module name
(Name)
New name of the module (max. 6 characters)
Response:
Valid Command:
Invalid Command: ?AA[CHKSUM](CR)
!
Delimiter for a valid command.
?
Delimiter for an invalid command.
AA
Address of the responding module (00 to
FF)
There will be no response if the command syntax is
incorrect, there is a communication error, or there is
no module with the specified address.
M-7065 User's Manual Ver2.0, Dec. /200 8 ---66
!AA[CHKSUM](CR)