2. DCON Protocol

All communication with M-7000 modules consists of
commands generated by the host and responses transmitted
by the M-7000 modules. Each module has a unique ID
number that is used for addressing purposes and is stored in
non-volatile memory. The ID is 01 by default and can be
changed using a user command. All commands to the
modules contain the ID address, meaning that only the
addressed module will respond. The only exception to this is
commands #**(Section 2.2) and ~** (Section 2.26), which
are sent to all modules, but in both of these cases, the
modules do not reply to the command.
Command Format:
Leading
Character
Response Format:
Leading
Character
CHKSUM 2-character checksum which is present when
the checksum setting is enabled.See Sections
1.1 (Data Format Setting) for details.
CR
End of command character, carriage return
(0x0D)
M-7065 User's Manual Ver2.0, Dec. /200 8 ---18
Module
Command
Address
Module
Address
[CHKSUM]
Data
[CHKSUM]
CR
CR