1 OVERVIEW

The powerful Microprocessor contained within the HAT520N ATS controller allows for precision voltage
(2-way 3-phase/single phase) measuring and make accurate judgment on abnormal voltage (power lost,
over/under voltage, over/under frequency, loss of phase, phase sequence wrong) and control ATS to
transfer after the delay has expired. This controller is suitable for NO Breaking ATS. When 1# power is
abnormal, the controller will send signal to start genset after the "1# abnormal delay" has expired. "Three
remote" (remote control, remote measurement and remote communication) function can be
implemented with the help of LINK communication port.

2 PERFORMANCE AND CHARACTERISTICS

HAT520N ATS controller owns performance and characteristics are shown as below,
a) Measure and display 2-way 3 phase Voltage and Frequency:
1#
Line voltage
Phase voltage (Ua, Ub, Uc)
Frequency
b) Over/under voltage, loss of phase, phase sequence wrong, over/under frequency protection
function. As default, phase sequence wrong protection and over/under frequency protection are
disable; however, users can set the protection function as need.
c) With LINK communication port (with SmartGen SG72 adapter). Parameters can be set via PC
software and also can realize firmware update of controller.
d) The voltage normal delay of 1# or 2#can be set in (0~60) seconds and the Genset start delay can
be set in (0~3600) seconds.
e) The voltage abnormal delay of 1# or 2#can be set in (0~60) seconds and the Genset stop delay
can be set in (0~3600) seconds.
"1# power priority", "Auto/Manual", "No priority" and "2#power priority" can be set via controller
f)
front panel.
g) Closing output signal can be set as on intervals or as continuous output.
h) Applicable for 2 isolated neutral line.
i)
Auto/Manual mode. In manual mode, ATS transfer 1# switch or 2# switch can be implemented via
panel pushbutton.
j)
LEDs mounted on front panel can clearly show ATS running status.
k) The output contactor capacity of 1# and 2#power supply transfer relay (1#CLOSE, 2#CLOSE) is
16A AC250V, volts-free contact, can be directly used in driving switch to transfer.
l)
The output contactor capacity of Genset start relay (GENS START) is 7A AC250V/7A DC28V,
volts-free N/C contact.
m) Suitable for various AC systems (3 phase 4-wires, 2-phase 3-wires and single-phase 2-wire).
n) Modular design, self extinguishing ABS plastic shell, pluggable terminal, built-in mounting,
compact structure with easy installation.
HAT520N ATS Controller
(Uab, Ubc, Uca)
Hz
HAT520N ATS CONTROLLER USER MANUAL
2#
Line voltage
(Uab, Ubc, Uca)
Phase voltage (Ua, Ub, Uc)
Frequency
Hz
Version 1.1
2017-08-02