Chapter 4. PROFINET System Operation
4.2
Operations of the PROFINET Controller in the
PACSystems System
The PROFINET IO-Controller in the PACSystems controller system performs the following operations:
Consumes PROFINET IO-Device configuration from the CPU and transfers it to the IO-Devices over
the PROFINET network.
Consumes input data from each PROFINET IO-Device and makes that data available to the CPU
during the CPU's input scan.
Produces the output data that it receives from the CPU during the CPU's output scan to each
PROFINET IO-Device.
Receives PROFINET alarms and diagnostics from PROFINET IO-Devices and converts them to a
PACSystems format.
Maintains a Local Log Table of its own alarms and the diagnostic information it receives. It also
forwards some of the information to the CPU as I/O or Controller Faults.
Automatically converts between the little-endian data format recognized by the CPU and the big-
endian format used for PROFINET communications.
Checks for duplicate IP Addresses as described below.
4.2.1

Duplicate PROFINET IO-Device IP Address

The PROFINET IO-Controller will detect an IP Address conflict between a device that it is configured to
communicate with and another device in two situations:
First, duplicates are detected when the PROFINET IO-Controller is trying to initially establish
communications with the configured PROFINET IO-Device. During the connection sequence, the PROFINET
IO-Controller queries the network to see whether any other node has the same IP Address as the
configured device.
Second, duplicates are detected whenever a network device announces its presence
the IP Address of that device is identical to that of a PROFINET IO-Device that the PROFINET Controller is
currently communicating with.
In both cases, the PACSystems PROFINET IO-Controller attempts to establish or maintain the connection and
logs a Duplicate IP Address Detected fault for the device. The PROFINET IO-Controller then periodically queries
the network for resolution of the IP Address conflict. If the IP Address conflict is resolved, the PROFINET IO-
Controller logs a Duplicate IP Address Resolved fault for the device.
5
The PROFINET Controller uses the ARP protocol to detect duplicate IP addresses. Devices that issue a gratuitous ARP to
announce their presence on the network are detected.
90
PACSystems* RX3i & RSTi-EP PROFINET IO-Controller User Manual
5
on the network and
GFK-2571N