6.2.4 Limits and Warnings
Parameter group for configuring limits and warnings.
4-11 Motor Speed Low Limit [RPM]
Range:
Function:
0 RPM
[0 - par.
Enter the minimum limit for motor speed.
*
4-13 RPM]
The Motor Speed Low Limit can be set to
correspond to the manufacturer's
recommended minimum motor speed. The
Motor Speed Low Limit must not exceed
the setting in 4-13 Motor Speed High Limit
[RPM].
4-13 Motor Speed High Limit [RPM]
Range:
Function:
1500.
[par. 4-11
Enter the maximum limit for motor speed.
RPM
- 60000.
The Motor Speed High Limit can be set to
*
RPM]
correspond to the manufacturer's
maximum rated motor. The Motor Speed
High Limit must exceed the setting in
4-11 Motor Speed Low Limit [RPM]. Only
4-11 Motor Speed Low Limit [RPM] or
4-12 Motor Speed Low Limit [Hz] will be
displayed, depending on other parameters
in the main menu, and depending on
default settings dependant on global
location.
NOTE!
Max. output frequency cannot exceed 10% of the carrier
frequency (14-01 Switching Frequency).
NOTE!
Any changes in 4-13 Motor Speed High Limit [RPM] will reset
the value in 4-53 Warning Speed High to the same value as
set in 4-13 Motor Speed High Limit [RPM].
Parameter group for configuring the digital input and
output.
5-01 Terminal 27 Mode
Option:
Function:
[0]
Input
Defines terminal 27 as a digital input.
*
[1]
Output
Defines terminal 27 as a digital output.