Bpm Signal Input Wire Routing - Eaton 9PXM8S4K User Manual

Table of Contents

Advertisement

BPM Signal Input Wire Routing

3 3 . . 4 4
B B P P M M S S i i g g n n a a l l I I n n p p u u t t W W i i r r e e R R o o u u t t i i n n g g
The auxiliary contacts must be wired to the BPM from the UPS for proper functionality. These auxiliary contacts
signal the UPS to go to Internal Bypass mode to provide a synchronized transfer. Failure to wire the auxiliary
contacts can be dangerous and result in system failure.
If the UPS is in standby mode and the bypass auxiliary contact is activated, the UPS output will become
energized.
1.
Route the maintenance bypass signal wires in a conduit from the bypass module to the communication
signal terminal (CN13) on the rear of the UPS ( See
electrical code.
2.
Place the signal wires through the proper conduit or grommet to the terminal block in the BPM.
Figure 20. UPS Input Control Signal Wiring for Maintenance Bypass
22
4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 10
Building Input
ROO and On Generator
(CN5)
(CN6)
4 3 2 1
4 3 2 1
Input signal
wires
FORCED
BYPASS IN
NEUTRAL
(red wire)
(black wire)
Bypass Module
Terminal
AUX NO
CONTACT
FORCED
BYPASS IN
(red wire)
ON UPS
(white wire)
BPM Signal
Terminals
Figure 20
Maintenance Bypass
EPO
(CN13)
(CN7)
3 2 1
4 3 2 1
Attach supplied
wire connectors to input wires
and plug into UPS
BYPASS
ON UPS
(white wire)
NO
CONTACT
FORCED
BYPASS IN
(red wire)
BYPASS
NEUTRAL
(black wire)
BYPASS
NEUTRAL
(black wire)
(Install conduit
over signal wires)
). For conduit requirements consult your local
External CAN to EBM
(CN4)
7 6 5 4 3 2 1
ON UPS
(white wire)
UPS Signal
Terminals

Advertisement

Table of Contents
loading

Table of Contents