6 PROTOCOL BLOCK
4
Click Apply.
5
Click OK.
Configuring field network tag names for the Drive devices
1
Click the Process Data menu in the Navigation Area.
The Danfoss VLT2880 PPO type 1 is used for illustration purposes.
The PPO type that you have selected appears in the right pane.
2
Click the
Configure the PKW inputs as "PKWIn" and PKW outputs as "PKWOut."
3
Configure the input PPO type PDCs as "CyclicIn" and output PPO type PDC as "CyclicOut."
4
74
www.honeywell.com
Attention
The network tag names must be unique within a slave device. However, you can use the same tag name for
another slave device. If there are identical tag names within a slave device, an error message appears when you
try to save the configuration.
The tag names must contain characters 0 – 9, a – z, A – Z, and one underscore (_).
If you have configured the Turck Excom devices to read HART data, you must configure two net tag names;
one for the first four words that represent the process data and one for the next words that represent the HART
data.
plus sign to expand all the inputs and outputs associated with the specific PPO type.
Attention
The PKW and cyclic data areas appear separated from each other. Based on the number of PKW and cyclic data
areas, you must configure the network tag names. In the example above, there are two inputs (PKW inputs and
Cyclic inputs) and two outputs (PKW outputs and Cyclic outputs). Therefore, you must configure four PDCs to
access this data.
Attention
If there are more than one input PPO type PDCs, you must configure the input PPO types as CyclicIn1,
CyclicIn2, and so on.
Similarly, if there are more than one output PPO type PDCs, you must configure the output PPO types as
CyclicOut1, CyclicOut2, and so on.
The remaining net tags must be used for PDCs which are of type "User Configurable," so that you can access
the PZD data in the way you require.
You must configure the network tags only for the first data items of the PKW and cyclic data areas.