Drive Dsb Specific Module Configuration In Profibus Network Configuration Tool; Genpadsb And Genpagwdsb Specific Module Configuration In Profibus Network Configuration Tool; Siemens Asi Link Dsb Specific Modules Configuration In Profibus Network Configuration Tool - Honeywell Experion PKS User Manual

Profibus gateway module
Hide thumbs Also See for Experion PKS:
Table of Contents

Advertisement

6 PROTOCOL BLOCK
Click OK.
13
14
Click Save
A message appears after you save the configuration.
Click OK.
15
Click OK to close the Field Network Configuration form.
16
The field network configuration is saved to the ERDB.

6.3.1 Drive DSB specific module configuration in Profibus Network Configuration Tool

The following list illustrates the Drive device specific module configuration guidelines that you must remember
while configuring the Drive device in "Profibus Network Configuration Tool ".
You can only select one PPO type for a Drive device.
6.3.2 GENPADSB and GENPAGWDSB specific module configuration in Profibus Network
Configuration Tool
The following list summarizes the GENPADSB and GENPAGWDSB specific PDC configuration guidelines
that you must remember while configuring the GENPADSB and GENPAGWDSB.
For Siemens DP/PA Link IM-157, you must use the customized GSD file that is generated from the GSD
Combiner tool.
While configuring the GENPAGWDSB for Siemens DP/PA Link IM-157, you must refer to the Siemens
DP/PA Link document.
While configuring the GENPAGWDSB, to support alarming based on diagnostic data received from
Siemens DP/PA Link IM-157, you must select the option 160 byte diagnostics data length from the
Parameters page.

6.3.3 Siemens ASi Link DSB specific modules configuration in Profibus Network Configuration Tool

The following list illustrates the Siemens AS-i Link device specific module configuration guidelines that you
must remember while configuring the Siemens AS-i Link device in "Profibus Network Configuration Tool".
For configuring the Siemens AS-i Link/Siemens AS-i Link Advanced device, the minimum configuration
required to support all 31 devices involves mapping every 4 bytes to a single net tag (in the field network
configuration). This means that you can leave some bytes with the default net tag name.
. While configuring the Siemens AS-i Link DSB for AS-I Link 20E device, you can only select the "max.
16/16 Byte AKF" module. Note that the "max. 32/32 Byte" module is not supported by the Siemens AS-i
Link DSB.
While configuring the Siemens AS-i Link DSB for AS-i Link Advanced device, you must select the Classic
layout which is the only layout supported by this DSB.
While configuring the Siemens AS-i Link DSB for the AS-i Link Advanced device, you can select "ASi-1:
Binary Array 16-byte" and/or "ASi-2: Binary Array 16-byte."
66
www.honeywell.com
on the Field Network Configuration tab toolbar.
Attention
When you click Save
, the configuration is saved temporarily.
Attention
If you click Cancel and close the configuration form, the configuration is not saved to the ERDB even if you have
clicked Save
on the Field Network Configuration tab toolbar.