Honeywell Experion PKS User Manual Page 261

Profibus gateway module.
Hide thumbs

Advertisement

Diagnostic Check Ensure that the Device Index switches on the IOTA were not intentionally set to zero to initiate a
Device Index/IP Address reset.
Cause 1
Device Index switches set to zero.
Solution
Change Device Index switches to correct setting.
Cause 2
The module is defective.
Solution
Replace the module.
If Device Index switch setting matches Device Index number in 4-character display upon PGM power
up, the removed module is defective. Otherwise, go to Cause 3.
Cause 3
The IOTA is defective.
Solution
Replace the IOTA.
If Device Index switch setting matches Device Index number in 4-character display upon PGM power
up, the removed IOTA is defective.
13 PROFIBUS GATEWAY MODULE (PGM) TROUBLESHOOTING
261