8 PROFIBUS HART INPUT/OUTPUT MODULE (PBHIOM) FUNCTION BLOCK
Restore Errors and Failure (RESETHCOMERR)
The Restore Errors and Failure (RESETHCOMERR) parameter resets HART communication diagnostic
parameters to their default values.

8.6.2 PBHCHANNEL HART Notification-related parameters

Scan Priority for Command 48 (HSCANCFGC48)
The Scan Priority for Command 48 (HSCANCFGC48) parameter can be low or high. The ratio of high to low
priority scan is configured in the DPV1 tab of the DSB level.
Command 48 Strings (HCMD48STRNGS)
The Command 48 Strings (HCMD48STRNGS) parameter displays the strings embedded in the DD file.
Notification Option (HCMD48NOTIFY)
The Notification Option (HCMD48NOTIFY) parameter indicates the notification option that you have
configured.
Attention
This parameter is not available in the device. However, this parameter can be configured to generate either an Event or
an alarm or View Only. By default, this parameter is set as "Event."

8.6.3 PBHCHANNEL HART Variables-related parameters

In the HART Variables tab, you can monitor the device variables and the dynamic variables of the
PBHCHANNEL.
Dynamic Variable Name (HDYNNAME)
The Name (HDYNNAME) parameter displays the HART digital variable name provided you for identifying the
variable..
Dynamic Variable Code (HDYNDVC)
The Variable Code (HDYNDVC) parameter displays the configured HART digital variable codes.
Dynamic Variable Descriptor (HDYNDSC)
The Descriptor (HDYNDSC) parameter displays the description provided for each HART digital variable.
Dynamic Variable Value (HDYNVAL)
The Value (HDYNVAL) parameter displays the configured value for each HART digital value.
Dynamic Variable Units (HDYNEU)
The Units (HDYNEU) parameter displays the engineering units provided for HART digital data.
Dynamic Variable Classification (HDYNCC)
The Classification (HDYNCC) parameter displays the classification code provided for each HART data.
202
www.honeywell.com
If the HCMD48NOTIFY is configured as "Event," then the notifications are available in Event Summary page.
If the HCMD48NOTIFY is configured as "Alarm," then the notifications are available in Alarm Summary page.
If the HCMD48NOTIFY is configured as "View Only," then the notifications are not available in Station and
available only in Control Builder.