Trouble Shooting

Temporarily Removing an Individual Base Device

26.1
It may be necessary to replace a device or temporarily removed it from the base. Once the
device is ready for replacement, it must be re-inserted at the exact location.
The steps may be performed when the detector circuit is enabled.
Siemens Industry, Inc.
Building Technologies Division
1. Remove the device.
 The control panel detects that the device is missing and reports a 'Trouble'.
2. Perform the necessary activities.
3. Re-insert the devices in the previous position.
4. Acknowledge the 'Trouble'.
 If the 'Trouble' is no longer displayed, the control panel updates the setting of
the re-inserted device.
 If the 'Trouble' is still displayed, and/or the 'Circuit' is not in normal operation,
the 'Circuit' has to be restarted.