366 Parameters

Status and control words

This table lists the FSO module and drive status and control words. You can view
these in the ACS880 window of Drive composer pro.
Index
Name/Value
Safety
200.01 FSO speed ch1
0.00 ... rpm
200.02 FSO speed ch2
0.00 ... rpm
200.03 FSO DI status
200.04 FSO DO status
Description
Shows the motor speed estimate 1 of the FSO module. The
FSO module reads the value from the drive via communication
channel 1.
Speed
FbEq16: 1 = 1 rpm; FbEq32: 100 = 1 rpm
Shows the motor speed estimate 2 of the FSO module. The
FSO module reads the source data from the drive via
communication channel 2 and calculates the speed estimate 2
using the data.
Speed
FbEq16: 1 = 1 rpm; FbEq32: 100 = 1 rpm
Shows the states of the FSO digital inputs.
Bit
Name
0
Input X113:1
1
Input X113:2
2
Input X113:3
3
Input X113:4
4
Input X114:1
5
Input X114:2
6
Input X114:3
7
Input X114:4
8-15 Reserved
Shows the states of the FSO digital outputs.
Bit
Name
0
Output X113:7
1
Output X113:8
2
Output X113:9
4
Output X114:7
5
Output X114:8
6
Output X114:9
7-15 Reserved
Values
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
Values
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On
0 = Off, 1 = On