226 PROFIsafe
6. To check the Device number of the FENA module, select the General tab.
Diagnostic messages related to F-Parameters
The diagnostics messages in this table are caused by problems in the
F-Parameter processing that takes place only when the controller station sends the
F-Parameters to FENA. This happens normally only when the controller station starts
up the PROFINET communication with the FENA module.
Value
Description
(hex)
64
Mismatch of safety destination
(0x0040)
address (F_Dest_Add).
65
Safety destination address is not valid
(F_Dest_Add).
(0x0041)
66
Safety source address is not valid
(F_Source_Add).
(0x0042)
67
Safety watchdog time value is 0 ms
(F_WD_Time).
(0x0043)
Notes
F_Dest_Add did not match the value
configured in the safety parameters
(PROFIsafe. 11 PROFIsafe
F_Dest_Add of 0 or FFFFh is not allowed.
A valid F_Dest_Add is within range
1...65534.
F_Source_Add of 0 or FFFFh is not
allowed.
A valid F_Source_Add is within range
1...65534.
Watchdog time 0 ms is not allowed.
A valid F_WD_Time is within range
1...65535.
F_Dest_Add).