294 Configuration

Configuring SAR

How to configure SARn

To configure the SARn (n = 0...1), set the FSO parameters listed below to appropriate
values using the Drive composer pro PC tool. See parameter groups
page
322
and
SARx
Example: The figure below shows an example of a SAR0 monitoring set-up:
• SAR0
• ramp time from Scaling speed to zero: 1000 ms
(200.102 SAR0 ramp time to zero
• Scaling speed: 1500 rpm
• initial range for monitoring: 100 ms
• minimum allowed ramp time: 500 ms
(SARx.11 SAR0 min ramp time to zero
• maximum allowed ramp time: 1000 ms
(SARx.12 SAR0 max ramp time to zero
SAR0
Speed
200.202
= 1500 rpm
on page 348. See also section
(200.202 SAR speed scaling
SARx.11
SARx.02
= 100 ms
Ramp monitoring
= 1000 ms)
(SARx.02 SAR initial allowed range
= 500 ms)
= 1500 ms).
= 500 ms
SARx.12
200.102 =
1000 ms
Safety
on
on page 51.
= 1500 rpm)
= 100 ms)
Time
= 1500 ms