102 Safety functions

SSE with immediate STO, with speed limit activated SBC

This safety function requires that you use an encoder in the safety application.
The operation of the SSE with immediate STO with speed limit activated SBC is
described in the time diagram and table below. For configuration, see section
configure STO with speed limit activated SBC
Motor speed
A
B
1
A
STO SBC speed (parameter SBC.14): Speed limit at which the FSO activates the SBC
function (brake).
B
Zero speed with encoder (parameter FSOGEN.52): Speed limit at which the motor has
stopped, the safety function is completed and the SSE completed indication (parameter
SSE.22) goes on. The acknowledgment becomes allowed.
Step
Description
1
The SSE request is received (for example, from the I/O). The FSO activates the drive
STO function.
2
The motor speed goes below the SBC speed limit (A) and the FSO activates the SBC
function (brake).
3
The motor speed goes below the zero speed limit (B), the FSO module defines the
motor as stopped and the SSE completed indication goes on. The acknowledgement
becomes allowed as soon as the SSE request has been removed (step 4).
4
The SSE request is removed.
5
After the acknowledgement, the STO, SSE and SBC functions are deactivated and the
control is given back to the drive, which controls the brake from now on. The
indications go off.
on page 270.
2
3
How to
Time
4
5
SSE request
Drive STO state
& indication
SSE state &
indication
SBC output
SSE completed
indication