Typical Communication Errors - ABB FSO-21 User Manual

Safety functions module
Hide thumbs Also See for FSO-21:
Table of Contents

Advertisement

Value
Description
(hex)
68
Parameter "F_SIL" exceeds SIL from
specific device application.
(0x0044)
69
Parameter "F_CRC_Length" does not
match the generated values.
(0x0045)
70
Parameter "F_Par_Version" set
incorrectly.
(0x0046)
71
CRC1 Fault
(0x0047)
72
Device-specific diagnosis information
(0x0048)

Typical communication errors

This table lists some typical error situations in the PROFINET and PROFIsafe
communication.
Fault
You cannot start
the PROFINET
communication.
Cause
The FENA station name saved in
the FENA does not match the
station name of the FENA in the
PLC configuration.
The FENA IP address saved in the
FENA does not match the IP
address of the FENA in the PLC
configuration.
The FENA is not configured for the
PROFINET communication.
Notes
F_SIL defined for this device at F-Host is
not correct. This device supports only
F_SIL = 3.
F-Parameter checksum length different
from 3 octets. This device supports only
three (3) octet CRC2.
Version of F-Parameter defined for this
device at F-Host is not correct. This device
supports only V2.
Checksum CRC1 calculated over the
F-Parameters does not match the
checksum value in the F-Parameters.
Unsupported PROFINET submodule
identification number received from the
controller station upon PROFINET
connection, or general error in the F-
Parameters.
What to do
Check the station names in both
places.
Check the IP settings in both places.
Check drive parameter 51.01 or
54.01. See the FENA user's manual
for details.
PROFIsafe 227