Configuring SS1

To configure the SS1 function, set the FSO parameters listed below to appropriate
values using the Drive composer pro PC tool. See parameter group
page 339.
For more information on the SS1 function, see page 68.

How to configure SS1 with time monitoring (SS1-t)

Example: The figure below shows an example of an SS1-t set-up:
• SS1 function activated
• SAR1 emergency ramp (always with the SS1 function)
• SS1 with time monitored ramp
• security delay for activating the drive STO: 2000 ms
(SS1.14 SS1-t delay for STO
• automatic acknowledgement
• redundant emergency stop button connected to input
(SS1.11 SS1 input A
• single output connected
• zero speed limit for activating the drive STO: 90 rpm
(FSOGEN.51 Zero speed without encoder
(when an encoder is used:
• delay for activating STO after the zero speed limit has been reached: 0 ms
(SS1.15 SS1-r ramp zero speed delay for STO
• speed limit activated brake not in use
(SBC.15 SSE/SS1 SBC speed
• See also section
(SS1.01 SS1 activity and version
(SS1.13 SS1 type
= 2000 ms)
(STO.02 STO acknowledgement
= DI X113:1 & X114:1)
(SS1.21 SS1 output
FSOGEN.52 Zero speed with encoder
= 0 ms).
Fine-tuning the configuration
= Version 1)
= SS1-t)
= DO X114:9)
= 90 rpm)
= 0 ms)
on page 314.
Configuration 273
SS1
on
= Automatic)
= 90 rpm)