Safety Data For Some Typical Configurations - ABB FSO-21 User Manual

Safety functions module
Hide thumbs Also See for FSO-21:
Table of Contents

Advertisement

Safety data for some typical configurations

The table below shows FSO-21 safety data for some safety functions with typical
combinations of the FSO module subsystems. See section
page
433
for more information on the subsystems.
Values without the FSE-31 module
Subsystems used
in the safety
function
Prevention of unexpected start-up / Emergency stop, with a safe output (eg, releasing a mechanical
brake)
1-channel pulsed DI
Logic 2
STO-output
3.7E-09
1-channel pulsed
output
1-channel non-
pulsed DI Logic 1
STO-output
7.6E-08
1-channel non-
pulsed output
2-channel pulsed DI
Logic 2
STO-output
7.7E-11
2-channel pulsed
output
2-channel non-
pulsed DI
Logic 2
7.8E-11
STO-output
2-channel non-
pulsed output
SLS, with a safe status output
Speed measurement
1-channel pulsed DI
Logic 2
1.0E-08
STO-output
1-channel pulsed
output
Speed measurement
1-channel non-
pulsed DI
Logic 1
8.2E-08
STO-output
1-channel non-
pulsed output
Speed measurement
2-channel pulsed DI
Logic 2
6.7E-09
STO-output
2-channel pulsed
output
Speed measurement
2-channel non-
pulsed DI
Logic 2
6.7E-09
STO-output
2-channel non-
pulsed output
PFH
PFD
avg
(1/h)
(T1 =2 a)
(T1 =5 a)
3.6E-05
6.8E-04
8.5E-07
8.6E-07
8.5E-05
7.3E-04
5.0E-05
5.0E-05
PFD
SFF
HFT
avg
(%)
8.4E-05
99.29
0
1.7E-03
92.26
0
1.9E-06
99.60
1
1.9E-06
99.59
1
2.0E-04
99.03
0
1.8E-03
98.39
0
1.2E-04
99.05
1
1.2E-04
99.05
1
Technical data 435
Basic safety data
SIL
MTTF
DC
D
SILCL
(a)
(%)
3
622.47
96.33
1
613.68
57.97
3
613.68
97.93
3
613.68
97.90
3
143.67
98.38
1
143.20
89.71
3
143.20
98.75
3
143.20
98.74
3AXD10000006135.xlsm G
on
Cat. PL
2
d
1
c
3
e
3
e
2
d
1
c
3
e
3
e

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents