308 Configuration

Configuring POUS

How to configure POUS

To configure the POUS function, set the FSO parameters listed below to appropriate
values using the Drive composer pro PC tool. See parameter group
page 335.
For more information on the POUS function, see page 145.
Example: The figure below shows an example of the POUS function set-up:
• POUS function activated
• automatic acknowledgement
• redundant POUS switch connected to inputs X113:1 and DIX114:1
(POUS.11 POUS input
• An additional security delay: 0
• POUS completed output (for example, an indication lamp) connected to single
output: X114:9
Input
Speed
POUS.11
= DI X113:1 &
X114:1
(POUS.01 POUS activity and version
(POUS.02 POUS acknowledgement
= DI X113:1 & X114:1)
(POUS.13 POUS delay for completion
(POUS.22 POUS completed output
POUS.01
POUS.02
POUS.13
POUS activated
= DO X114:9).
= Version 1
= Automatic
= 0 ms
POUS
on
= Version 1)
= Automatic)
= 0 ms)
Outputs
POUS.21
= None
POUS.22
= DO X114:9
Time