Parameter
AT_TYPE
TUNING_CRITERIA
TUNE_REQ
ATI
AT_MODE
AT_ERROR
AT_GAIN
AT_RESET
AT_RATE
LICENSE_STATUS_
PID

Attributes

Supported
Modes
Alarm Types
Status
Handling
Revision 4
Foundation Fieldbus RMA803 Remote Indicator User's Guide
Auto Tune Selection supports two types: Disable, Cycle Tune.
Tuning Criteria supports two types: Normal, Fast.
Tuning Request performs auto tuning process.
Auto Tune Indicator indicates Auto tune ON/OFF.
Auto Tune Mode supports two options: AT Ready, Inactive
AT Ready indicates block is ready for auto tune
Inactive indicates auto tuning is disabled.
Auto Tune Error supports the following errors:
Abort, Not ready, OK, and Run.
Auto tuned Gain.
Auto tuned Reset.
Auto tuned Rate.
License status of the function block.
The block supports the following modes:
AUTO (Automatic)
MAN (Manual)
OOS (Out of Service)
IMan
Cas
RCas
ROut
LO
The block supports standard block alarms (see section 5.2), in
addition to it standard HI_HI, HI, DV_HI, DV_LO, LO, and LO_LO
alarms applied to PV.
Standard, in addition to the following things for the control selector.
If Not selected is received at BKCAL_IN, the PID algorithm must
make necessary adjustments to prevent windup.