Hart For Safety-Related Applications - Siemens SIMATIC 6DL1 136-6AA00-0PH1 Manual

F-ai 8xi 2-/4-wire hart ha i/o module
Table of Contents

Advertisement

DATA:
CHK:
With the exception of the preamble bytes, this structure is contained in the communication data
of the HART command interface.
HART request and response data records (Page 97)
HART responses always contain data. Status information (HART device status; 1st and 2nd status
bytes) is always sent together with a HART response. You should evaluate the status information
to ensure that the response is correct.
8.1.4

HART for safety-related applications

Overview
SIL-3 application for channels with HART devices without write protection
For SIL-3 applications for channels with HART devices without write protection, please note that
as soon as you activate the "HART-Tor" parameter, the input values of the channels must be
checked for plausibility, for example by comparison with the equivalent value of another I/O
module in the user program.
Optionally, the I/O module can also be removed from the safety function of the plant for this
time.
FAIW-022
F-AI 8xI 2-/4-wire HART HA
Equipment Manual, 09/2021, A5E50557845-AA
Transferred user data / parameters, quantity depending on command (0...230
bytes)
Checksum
WARNING
HART function
8.1 Use
77

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic et 200sp ha

Table of Contents