A.1 Vs1Gv Specifications - Baldor VS1GV21-1B Installation & Operating Manual

Vs1gv series ac closed vector control
Table of Contents

Advertisement

A.1 VS1GV Specifications

Voltage
Voltage Range
Input Ratings
Phase
Frequency
Impedance
Horsepower
Overload
Output Ratings
Capacity
Frequency
Voltage
Feedback Type
Pulses/Rev
Voltage Output
Motor
Marker Pulse
Feedback
Power
Max. Frequency
Positioning
Vector Trip
Stall Prevention
Protective
External Output
Features
Short Circuit
Electronic Motor
Overload
Temperature
Cooling
Enclosure
Altitude
Environmental
Conditions
Humidity
Shock
Vibration
Transportation
and Storage
Temperature
Duty Cycle
Note: H2D, H2E, and H2F-Frame drives are not permitted to be applied in single-phase input applications. Additionally, the
H2B-Frame NEMA 4X drive is not designed for single-phase input power.
MN765
Table A-1 VS1GV Specifications
120
240
95-130
180-264
Single Phase (1-3HP only)
50/60Hz ±5%
1% minimum from mains connection (3% minimum for AA frame drives)
¾-3 HP, 3PH output @ 120/240VAC, 1PH input
¾-500 HP @ 480VAC, 3PH input
Constant Torque (Heavy Duty) = 150% for 60 seconds, 175% for 3 seconds
Variable Torque (Normal Duty) = 115% for 60 seconds
0-500Hz
0 to maximum input voltage (RMS)
Incremental encoder coupled to motor shaft; optional resolver feedback
60-20,000 selectable, 1024 standard
2 channel in quadrature, 5VDC or 12VDC, differential
Required for position orientation
5VDC, 250mA maximum/ 12V, 200mA maximum
4 MHz
Buffered encoder pulse train output for position loop controller
Missing control power, over current, over voltage, under voltage, motor over speed,
encoder loss, over temperature (motor or control), output shorted or grounded, motor
overload
Over voltage suppression, over current suppression
LED trip condition indicators, 4 assignable logic outputs, 2 assignable analog outputs
Phase to phase, phase to ground
Meets UL508C (I
T)
2
-10°C to 45°C (40
C for B-Frame NEMA 4X drive)
o
Derate 3% per degree C above 45°C to 55°C maximum ambient temperature
(40
C- 50
C for B-Frame NEMA 4X drive)
o
o
Forced air
NEMA 1, IP20 (-1, -1T, -1B); NEMA 4X, IP66 (-4B), indoor mounting only.
Note: NEMA 4X/IP66 is not available in frame sizes C, D, E and F as a stock product but
can be supplied as part of a packaged drive.
Sea level to 3300 Feet (1000 Meters) Derate 2% per 1000 Feet (303 Meters) above 3300
Feet
10 to 90% RH Non-Condensing (NEMA 1); to 100% (NEMA 4X)
1G
0.5G at 10Hz to 60Hz
-30°C to +65°C
1.0
Appendix A
Technical Specifications
240
480
180-264
340-528
Three Phase (single phase with derating)
¾-60 HP @ 240VAC, 3PH input
¾-300 HP @ 600VAC, 3PH input
Technical Specifications A-1
600
515-660

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents