Trace Displays Continued
Action
Fault Trace Display
Fault Trace Display
Fault Trace Display
Fault Trace Display
Hexadecimal
MN765
Description
Third word in the event trace is
the V oltage reference for the
Analog to Digital Converter.
Next is the Voltage measurement
of the Internal 24V power supply
for the Opto Inputs and Outputs.
Next is the status of the nine
Digital Input signals.
J2
8 (Enable) left most digit=1.
J2 16 (DIN#8) right most digit=0.
Next is the status of the Digital
Output signals. The below table
indicates the function of each of the
8 bits.
Digital Output Display
Binary
00
0000 0000
01
0000 0001
02
0000 0010
04
0000 0100
08
0000 1000
10
0001 0000
20
0010 0000
40
0100 0000
80
1000 0000
Display
FAULT TRACE
EV. LOG
ADC CURRENT REF
1.501 V
STATUS
T0003
BACK
FAULT TRACE
EV. LOG
24 V REF
25.7 V
STATUS
T0003
BACK
FAULT TRACE
EV. LOG
USER INPUTS
100000000
STATUS
T0003
BACK
FAULT TRACE
EV. LOG
DIGITAL OUTPUTS
00010010
STATUS
T0003
BACK
Description
No Fault
Actual Speed is less than Zero Speed Band
Main SCR enable (active low)
Dynamic Brake active
Soft start (pre-charge) relay active
Relay Output 2 (J3-28, 29, 30) active
Relay Output 1 (J3-25, 26, 27) active
Digital Output 2 (J2-19, 20) active
Digital Output 1 (J2-17, 18) active
Comments
or
Press
to view next entry.
Press
or
to view next entry.
or
Press
to view next entry.
This is a bit display, not a hex
value.
Press
to view next entry .
or
This is a bit display , not a hex
value.
Troubleshooting 9-3