5.5.8 3 Speed Analog 2-Wire

Provides 2-wire input control and allows selection of 3 Preset Speeds. The values of the Preset Speeds are set in the Level
1 Preset Speeds block, Preset Speed 1, Preset Speed 2 and Preset Speed 3. The opto inputs can be switches as shown in
Figure 5-12 or logic signals from another device.
J1
1
2
3
4
5
6
7
See recommended tightening torques in Table A-2.
*Note: Remove factory jumper from J2-8 and J3-24 before connecting switch at J2-8.
J2-8
CLOSED allows normal control operation.
OPEN disables the control and the motor coasts to a stop.
J2-9
CLOSED operates the motor in the Forward direction (with J2-10 open).
OPEN motor decels to stop.
J2-10
CLOSED operates the motor in the Reverse direction (with J2-9 open).
OPEN motor decels to stop.
Note: Closing both J2-9 and J2-10 at the same time will reset a fault.
J2-11
CLOSED selects Analog Input 1.
OPEN selects Level 1 Input block, Command Source parameter.
Note: If Command Source (Level 1 Input block) is set to Analog Input 1, then Analog Input 1 is always selected
regardless of this switch position.
J2-12
CLOSED selects STOP/START and Reset Commands from the terminal strip.
OPEN selects STOP/START and Reset Commands from the keypad.
J2-13
CLOSED selects Level 1 Input block, Command Source parameter.
OPEN selects speed commanded from Keypad.
Note: When changing from Terminal Strip to Keypad (J2-12 or J2-13) the motor speed and direction will remain
the same after the change.
J2-14
Selects Preset Speeds as defined in the Speed Select Table (Table 5-8).
J2-15
Selects Preset Speeds as defined in the Speed Select Table (Table 5-8).
J2-16
Optional External Trip input (not required). If used, you must set Level 2 Drive Protect block, External Trip to "ON".
CLOSED allows normal operation.
OPEN causes an External Trip to be received by the control (when programmed to "ON").
J2-14
OPEN
CLOSED
OPEN
CLOSED
Note: When command source is a unipolar signal (0-10V, 0-5V, 4-20mA, etc.) and forward run or reverse run is closed,
motion will occur (unless both forward run and reverse run are closed at the same time).
5-12 Control Wiring
Figure 5-12 3 Speed Analog 2-Wire Connection Diagram
User Analog Return
Analog Input 1
Analog Ref. Power +
Analog Input 2+
Analog Input 2-
Analog Output 1
Analog Output 2
See Figure 5-4 for
connection information.
Table 5-8 Speed Select Table
J2-15
OPEN
Level 1, Input Setup, Command Source (parameter P1402)
OPEN
Preset 1
CLOSED
Preset 2
CLOSED
Preset 3
*
Enable
Forward Run
Reverse Run
Analog Input Select
Run Command
Speed Command
Switch 1
Switch 2
External Trip
Command
J2
8
Enable
9
Digital Input 1
Digital Input 2
10
11
Digital Input 3
Digital Input 4
12
13
Digital Input 5
Digital Input 6
14
Digital Input 7
15
16
Digital Input 8
17
Digital Output 1 + (Collector)
18
Digital Output 1 - (Emitter)
19
Digital Output 2 + (Collector)
20
Digital Output 2 - (Emitter)