7.3 Level 3 Parameters (Advanced Prog, Level 3 Blocks)

Parameter (Number)
Block Title
PROFILE
NUMBER OF CYCLES (3001)
RUN
PR RESTART MODE (3002)
SPEED CURVE 1 (3003)
SPEED CURVE 2 (3005)
SPEED CURVE 3 (3007)
SPEED CURVE 4 (3009)
SPEED CURVE 5 (3011)
SPEED CURVE 6 (3013)
SPEED CURVE 7 (3015)
PROFILE TIME 1 (3004)
PROFILE TIME 2 (3006)
PROFILE TIME 3 (3008)
PROFILE TIME 4 (3010)
PROFILE TIME 5 (3012)
PROFILE TIME 6 (3014)
PROFILE TIME 7 (3016)
MASTER PPR (3101)
PULSE
FOLLOW-
ER
INPUT VOLTS (3102)
INPUT TYPE (3103)
MN765
Table 7-3 Level 3 Parameter Block Definitions
Selection (Value)
Preset Value: 0
Range: 0 - 255
Sets the number of cycles that the profile will automatically run before
stopping.
Preset Value: 0
Range: 0 - 1
Restart (0) If interrupted, profile will start from the first step.
Continue (1) If interrupted, profile will start from current step.
Sets the restart mode if Profile Run is interrupted.
Preset Value: 0
Preset Value: 0
Preset Value: 0
Preset Value: 0
Preset Value: 0
Preset Value: 0
Preset Value: 0
Range: 0 - 3
FWD-Group1 (0) FWD-ACC/DEC Group1
REV-Group1 (1) REV-ACC/DEC Group1
FWD-Group2 (2) FWD-ACC/DEC Group2
REV-Group2 (3) REV-ACC/DEC Group2
Speed for curve is set by the value of the correlating Preset Speed.
Preset Value: 0.00
Preset Value: 0.00
Preset Value: 0.00
Preset Value: 0.00
Preset Value: 0.00
Preset Value: 0.00
Preset Value: 0.00
Range: 0 - 65535.00 seconds
Sets the amount of time Profile Run stays at a preset speed. Time starts
when speed is within the At Speed Band P1506. ACC/DEC times are not
included. A setting of zero causes an immediate transition to the next speed
segment after the current segment is within the speed band. (See also 1506.)
Preset Value: 1024
Range: 50 - 20000 counts
The number of encoder pulses per revolution of the master encoder. (See
also MN755.)
Preset Value: 0
Range: 0 - 1
5V (0) Encoder operating voltage is 5V.
12V (1) Encoder operating voltage is 12V.
Preset Value: 1
Range: 0 - 2
None (0) No encoder input signal to the EXBHH007 expansion board.
Quadrature (1) Quadrature encoder input signal to the EXBHH007 expansion board.
Speed (2) Speed encoder input signal to the EXBHH007 expansion board.
Parameter Name and Description
Parameter Descriptions 7-31

Hide quick links:

Advertisement

Table of Contents
loading