10.5 PLC Mode as Standard Run 2-Wire Mode

This example shows how the PLC Mode may operate as the Standard Run 2-Wire Mode.
These parameter values are entered from the keypad.
Initialization:
Parameter
P1401
PLC Mode configuration parameters:
Parameter
Parameter Dec
Number
P3401
050.000.000.020
P3402
051.000.000.021
P3403
052.000.053.018
P3404
052.000.000.006
P3405
053.000.000.005
P3406
054.000.000.022
P3407
055.000.000.024
P3408
056.000.000.023
P3409
057.003.000.019
10K Pot or
0 - 10 VDC
See recommended tightening torques in Table A-2.
*Note: Remove factory jumper from J2-8 and J3-24 before connecting switch at J2-8.
The Parameter Dec Value column can be used when entering the PLC configuration parameters at the keypad (parameters
are shown as decimal long values - byte3.byte2.byte1.byte0).
For this mode Enable is active.
Note that Preset Speed 1 is active so the Preset Speed Select Table Index need not be programmed since it automatically
follows action 24 (Presets/Analog)
Jog is enabled anytime input 3 or 4 is on while these same inputs set the direction for jog.
The Fault action is programmed to trigger whenever digital input 8 goes low.
10-8 PLC Mode Description
Value
PLC
Byte 3 Condition
Value
Input 1 (50)
Input 2 (51)
Input 3 (52)
Input 3 (52)
Input 4 (53)
Input 5 (54)
Input 6 (55)
Input 7 (56)
Input 8 (57)
J1
1
User Analog Return
2
Analog Input 1
3
Analog Ref. Power +
4
Analog Input 2+
5
Analog Input 2-
6
Analog Output 1
7
Analog Output 2
PLC operating mode selected
Byte 2 Logic
Byte 1 Condition
OR (0)
OR (0)
OR (0)
OR (0)
OR (0)
OR (0)
OR (0)
OR (0)
NOR (3)
*
See Figure 5-4 for connection information.
Comment
Byte 0 Action
False (0)
Forward (20)
False (0)
Reverse (21)
Input 4 (53)
Jog Enable (18)
False (0)
Jog Forward (6)
False (0)
Jog Reverse (5)
False (0)
Acc/Dec Group (22)
False (0)
Presets/Analog (24)
False (0)
Reset (23)
False (0)
Fault (19)
J2
Enable
8
Enable
Forward Run
9
Digital Input 1
Reverse Run
10
Digital Input 2
Jog Forward
11
Digital Input 3
Jog Reverse
12
Digital Input 4
Accel/Decel Select
13
Digital Input 5
Preset Speed #1
14
Digital Input 6
Fault Reset
15
Digital Input 7
Fault
16
Digital Input 8
17
Digital Output 1 + (Collector)
18
Digital Output 1 - (Emitter)
19
Digital Output 2 + (Collector)
20
Digital Output 2 - (Emitter)
MN765