5.5.5 Fan Pump 2-Wire

Operation in the Fan Pump 2-wire mode is controlled by the opto isolated inputs at J2-8 through J2-16. The opto inputs can
be switches as shown in Figure 5-9 or logic signals from another device.
J2-8
CLOSED allows normal control operation.
OPEN disables the control and the motor coasts to a stop.
J2-9
CLOSED operates the motor in the Forward direction (with J2-10 open).
OPEN motor decels to stop. Note: J2-9 and J2-10 are both closed = Fault Reset.
J2-10
CLOSED operates the motor in the Reverse direction (with J2-9 open).
OPEN motor decels to stop. Note: J2-9 and J2-10 are both closed = Fault Reset.
J2-11
CLOSED selects Analog Input 1 (if J2-13, J2-14 and J2-15 are closed).
OPEN selects Command Source (Level 1, Input, Command Source) if J2-13, J2-14 and J2-15 are closed.
J2-12
CLOSED selects STOP/START and Reset commands from terminal strip.
OPEN selects STOP/START and Reset commands from Keypad.
J2-13
CLOSED allows other selections, see Speed Select Table 5-5.
OPEN selects speed commanded from Keypad (if J2-14 and J2-15 are closed).
Note: When changing from Terminal Strip to Keypad (J2-12 or J2-13) the motor speed and direction will remain
the same after the change.
J2-14
Firestat. Selects Level 1, Preset Speeds, Preset Speed 1.
J2-15
Freezestat. Level 1, Preset Speeds, Preset Speed 2 (if J2-14 is closed).
J2-16
Optional External Trip input (not required). If used, you must set Level 2 Drive Protect block, External Trip to "ON".
CLOSED allows normal operation.
OPEN causes an External Trip to be received by the control (when programmed to "ON").
J2-11
J2-13
OPEN
OPEN
CLOSED
CLOSED
CLOSED
Note: When command source is a unipolar signal (0-10V, 0-5V, 4-20mA etc.) and forward or reverse are closed, motion will
occur (unless both are closed at the same time).
MN765
Figure 5-9 Fan Pump 2-Wire Connection Diagram
J1
1
User Analog Return
2
Analog Input 1
3
Analog Ref. Power +
4
Analog Input 2+
5
Analog Input 2-
6
Analog Output 1
7
Analog Output 2
See Figure 5-4 for
connection information.
See recommended tightening torques in Table A-2.
*Note: Remove factory jumper from J2-8 and J3-24 before connecting switch at J2-8.
Table 5-5 Speed Select Table – Fan Pump 2-Wire
J2-14
J2-15
CLOSED
CLOSED
OPEN
CLOSED
OPEN
CLOSED
CLOSED
CLOSED
CLOSED
*
Enable
Forward Run
Reverse Run
Analog Input Select
Run Command
Speed Command
Firestat
Freezestat
External Trip
Keypad Speed Command
Level 1, Preset Speeds, Preset Speed 1
Level 1, Preset Speeds, Preset Speed 2
Level 1, Input Setup, Command Source (parameter P1402)
Analog Input 1
J2
8
Enable
9
Digital Input 1
Digital Input 2
10
11
Digital Input 3
12
Digital Input 4
13
Digital Input 5
14
Digital Input 6
Digital Input 7
15
16
Digital Input 8
17
Digital Output 1 + (Collector)
18
Digital Output 1 - (Emitter)
19
Digital Output 2 + (Collector)
20
Digital Output 2 - (Emitter)
Command
Control Wiring 5-9