Baldor VS1GV21-1B Installation & Operating Manual page 96

Vs1gv series ac closed vector control
Table of Contents

Advertisement

Parameter (Number)
Block Title
DRIVE
POWER INPUT (2110)
CONFIG
(Continued)
Common Bus Master (3)
BUS VOLT FILTER (2111)
Only available or active in V/F.
Ignore for either Vector mode.
EXECUTE MACRO (2112)
UNDO MACRO (2113)
TORQ ENABLE SEQ (2114)
Torque On Command (1)
DRIVE
EXTERNAL TRIP (2201)
PROTECT
7-18 Parameter Descriptions
Table 7-2 Level 2 Parameter Block Definitions Continued
Selection (Value)
Preset Value: 2
Range: 0 - 3
The output values are derated for single phase operation.
Note: For three phase power input, if a phase is lost this parameter will
Single Phase (0)
automatically be changed to single phase and the control will automatically
be derated for single phase operation.
Selected when only DC input power (master) is available. Do not choose if
Common Bus Slave (1)
AC power is connected. Common bus setting disables precharge and soft
start features of the control.
Three Phase (2) Standard operation.
Selected for special installations, three phase with common bus slave
support.
The Power base senses the control power base (single or three phase). If
connecting a three phase control to a single phase power source, change
value from 2 to 0 to avoid "Loss of Phase" trips.
Preset Value: 10.00
Range: 0.10 - 1000.00 Hz
Sets the cutoff frequency for the BUS Voltage Filter (used to demodulate the
BUS).
Preset Value: 0
Range: 0 - 5
No (0) Do not execute macro.
M1 (1) Execute Macro M1.
M2 (2) Execute Macro M2.
M3 (3) Execute Macro M3.
M4 (4) Execute Macro M4.
M5 (5) Execute Macro M5.
Executes the selected macro one time. A macro is a list of parameter
numbers and values that when executed set the respective parameters in the
list to the predefined values.
Preset Value: 0
Range: 0 - 1
No (0) Don't undo macro.
Value in the parameter Macro Status (P116) is read and that macro is undone
Yes (1)
(factory settings are restored for values modified by that macro).
Preset Value: 0
Range: 0 - 1
Torque On Enable (0) Regulates motor torque any time the drive is enabled.
Regulates motor torque only after the drive has received a run forward or run
reverse command.
This parameter determines whether the drive starts regulating motor torque
immediately upon closure of the drive enable input (J2-8) or only after the
drive receives a forward/reverse command input. Only effective during
remote operation while in open/closed vector mode.
Preset Value: 0
Range: 0 - 1
Off (0) External Trip is Disabled.
External Trip is enabled. If a normally closed contact at J2-16 is opened, an
On (1)
External Trip fault will occur and cause the drive to shut down.
Parameter Name and Description
MN765