Baldor VS1GV21-1B Installation & Operating Manual page 86

Vs1gv series ac closed vector control
Table of Contents

Advertisement

Parameter (Number)
Block Title
OUTPUT
DIGITAL OUTPUT 1 (1501)
SETUP
DIGITAL OUTPUT 2 (1502)
RELAY OUTPUT 1 (1503)
(Continued)
RELAY OUTPUT 2 (1504)
(Continued)
Curr Underload (12) Active when motor current is less than "Underload Set Point (P1509)".
Keypad Control (14) Active when control is in Local keypad control.
Dynamic Brake (15) Active when Dynamic Brake transistor is turned ON.
Command Forward (19) Active during forward run command.
Command Reverse (20) Active during reverse run command.
ZERO SPD SET PT (1505)
AT SPD BAND (1506)
SET SPEED POINT (1507)
7-8 Parameter Descriptions
Table 7-1 Level 1 Parameter Block Definitions Continued
Selection (Value)
Active when motor speed is within band set by the Level 1 Output Setup "At Speed
At Speed (9)
Band (P1506)".
Active when output speed is at or greater than the Level 1 Output Setup "Set
At Set Speed (10)
Speed Point (P1507)".
Curr Overload (11) Active when motor current is greater than "Overload Set Point (P1508)".
I
T Overload (13) Active when overload left is less than 100%.
2
Foldback (16) Active when current foldback is active (V/Hz Mode only).
Fault (17) Active when a fault condition is present (will cause trip).
Alarm (18) Active when an Alarm condition is present (but doesn't cause trip).
Motor Forward (21) Active when motor is moving in Drive forward direction.
Motor Reverse (22) Active when motor is moving in Drive reverse direction.
Process Error (23) Active when absolute process error is greater than P2606 (Process Error Tolerance).
Network (24) Active when commanded by network. Network device controls this output.
Active when load is at position (|Position error|≤P1517) AND
At Position (25)
(|Motor Speed|≤P1505).
In Motion (26) Active when load is moving (|Position error|>P1517) OR (|Motor Speed|>P1505).
PLC (27) Output is controlled by PLC mode.
RTC (28) Output is controlled by RTC module.
Powered Up (29) Active when Bus is "UP" and no faults are present.
If drive is disabled, output turns on when table switch is commanded and will turn
Par Tbl Switch (30)
off when completed.
Heater (31) Output turns on when trickle current heating is active.
See also 1505, 1506, 1507, 1508, 1509, 1517, Chapter 10, Chapter 11, Chapter 12.
Preset Value: 180
Range: 0 - MAX Speed RPM
A digital output programmed to "At Zero Speed" becomes active when motor
speed becomes less than this setting for vector modes or when speed demand
is less than this setting when in V/F mode. This is useful when a motor brake is to
interlock operation with a motor.
Preset Value: 60
Range: 0 - MAX Speed RPM
A digital output programmed to "At Speed" becomes active when the speed error
for vector modes or when the reference minus the demand for V/F mode is less
than the value set in this parameter.
Preset Value: 1800
Range: 0 - MAX Speed RPM
A digital output programmed to "At Set Speed" becomes active when the motor
speed is greater than the value programmed in this parameter for vector modes or
when the speed demand is greater than the value programmed in this parameter
for V/F mode.This is useful when another machine must not start or stop until the
motor exceeds a predetermined speed.