118 Technical data
Type ACS180-
Frame
04...
25A0-4
R3
033A-4
R3
038A-4
R4
045A-4
R4
050A-4
R4
1) Ratings in the tables are maximum for the given circuit breaker frame size. Breakers of the same frame
size and interrupting rating with lower current ratings are also allowed.
2) Drives that have an Minimum Enclosure Volume listed must be mounted in an enclosure ≥ Minimum
Enclosure Volume specified in this table.
3) When multiple drives that have an Enclosure Minimum Volume specified are installed in the same
enclosure, minimum volume of the enclosure is determined by largest Enclosure Minimum Volume of
the drives to be placed in the enclosure, plus the volume(s) of each additional drive.
4) Enclosures for R3, 240V and R3, 480V drives must have a solid bottom directly below the drive i.e. fans
(other than internal stirring fans), filters or louvers cannot be mounted directly below the drive but
can be mounted in adjacent areas on the bottom of the enclosure.
Manual self-protected combination motor controller – Type E USA
(UL (NEC))
You can use the ABB Type E manual motor protectors (MMP) MS132 & S1-M3-25,
MS165-xx and MS5100-100 as an alternative to the recommended fuses as a means
of branch circuit protection. This is in accordance with the National Electrical Code
(NEC). When the correct ABB Type E manual motor protector is selected from the
table and used for branch circuit protection, the drive is suitable for use in a circuit
capable of delivering no more than 65 kA rms symmetrical amperes at the maximum
rated voltage of the drive. See the table below for the appropriate MMP types and
minimum enclosure volume of IP20 / UL open type drive mounted in an enclosure.
If you use a manual motor protector for the branch circuit protection of the drive,
install the drive into a metal enclosure.
Note: The UL Listing of drive and MMP combinations applies only to drives that
are mounted in appropriately sized metal enclosures that are capable of containing
any drive component failure.
Type ACS180-
Frame
04...
1-phase U n = 208 ... 240 V
02A4-1
R0
03A7-1
R0
Breaker type(UL)
4)
SU203M-C50
4)
SU203M-C50
Contact ABB
Contact ABB
Contact ABB
MMP type
MS132-6.3 & S1-M3-25
MS132-10 & S1-M3-25
Minimum enclosure volume
1)
Minimum enclosure volume
1) 2) 3)
5)
5)
2) 3)
dm 3
in 3
30.3
1850
30.3
1850
75
4577
75
4577
75
4577
dm 3
in 3
15
890
15
890
4)