Typical power cable sizes
Drive type
Framesize
ACS560
3-phase U N = 400 V (380...480 V)
02A6-4
03A3-4
04A0-4
05A6-4
07A2-4
09A4-4
12A6-4
017A-4
025A-4
033A-4
039A-4
046A-4
062A-4
073A-4
088A-4
106A-4
145A-4
169A-4
206A-4
246A-4
293A-4
1) The cable sizing is based on maximum parallel layout of 6 cables laid on a cable ladder side by side,
ambient temperature 30 °C, PVC insulation, surface temperature 70 °C (EN 60204-1 and IEC
60364-5-52/2001). For other conditions, size the cables according to local safety regulations, appropriate
input voltage and the load current of the drive.
2) Aluminum cables must not be used with frames R0...R4.
3) In the USA, aluminum cables must not be used.
Cu cable type
mm 2
R0
3 × 1.5 + 1.5
R0
3 × 1.5 + 1.5
R0
3 × 1.5 + 1.5
R0
3 × 1.5 + 1.5
R0
3 × 1.5 + 1.5
R0
3 × 2.5 + 2.5
R1
3 × 2.5 + 2.55
R2
3 × 2.5 + 2.5
R2
3 × 6 + 6
R3
3 × 10 + 10
R3
3 × 10 + 10
R3
3 × 16 + 16
R4
3 × 25 + 16
R4
3 × 35 + 16
R5
3 × 35 + 16
R5
3 × 50 + 25
R6
3 × 95 + 50
R7
3 × 120 + 70
R7
3 × 150 + 70
R8
2 × (3 × 70 +
35)
R8
2 × (3 × 95 +
50)
1)
IEC
Cu cable type
AI cable
2)
type
mm 2
AWG/kcmil
-
-
-
-
-
-
-
-
-
-
-
-
3 × 35
3 × 50
3 × 70
3 × 70
3 × 120
3 × 150
250 MCM
3 × 240
300 MCM
2 × (3 × 95)
2 × (3 × 120)
Technical data 131
US
AI cable
3)
type
AWG/kcmil
16
-
16
-
16
-
16
-
16
-
14
-
14
-
14
-
10
-
8
-
8
-
6
-
4
-
2
-
2
-
1/0
-
3/0
-
-
-
2 × 2/0
-
2 × 3/0
-
EN
HI