Table 58: Description Of Marking Example For Approved Ex I I/O Modules According To Atex And Iecex - WAGO -I/O-SYSTEM 750 Manual

Can gateway
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-658 CAN Gateway
Table 58: Description of Marking Example for Approved Ex i I/O Modules According to ATEX and
IECEx
Gases
II
3(1)G
3(2)G
Ex
nA Gc
[ia Ga]
[ia Gb]
IIC
T4
Pos : 105.9 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 1.2.0, valid from FW/HW-Version 01/01
Use in Hazardous Environments
Equipment group: All except mining
Category 3 (Zone 2) equipment containing a safety
device for a category 1 (Zone 0) equipment
Category 3 (Zone 2) equipment containing a safety
device for a category 2 (Zone 1) equipment
Explosion protection mark
Type of protection and equipment protection level
(EPL): Non-sparking equipment
Type of protection and equipment protection level
(EPL): associated apparatus with intrinsic safety
circuits for use in Zone 0
Type of protection and equipment protection level
(EPL): associated apparatus with intrinsic safety
circuits for use in Zone 1
Explosion group of gas and vapours
Temperature class: Max. surface temperature 135°C
97

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-658

Table of Contents