Protocols Supported by Mailbox 2.0
Messages can be exchanged between different devices using the Mailbox 2.0
transfer procedure. Messages that are exchanged can be read by the
communication partner only when they are structured in line with a known
protocol. The Mailbox 2.0 transfer procedure uses the field "Protocol ID" of the
expanded header to identify the protocol being used.
Each of the transmitted messages consists of the header and a protocol data unit
(PDU) whose length and structure are based on the specific protocol.
Pos : 97 /Serie 750 ( WAGO-I/O-SYST EM)/Anhang/M ailbox 2.0 - Protokolle - unterstütz te Protokoll e 750-658 @ 16\mod_1371736131625_21.doc x @ 123869 @ @ 1
The I/O module supports the following protocols:
Table 33: Protocols Supported by Mailbox 2.0
Protocol ID Protocol Name Description
0x80
0x81
Pos : 98 /All e Seri en (Allgemei ne Module)/M ailboxkommuni kation/M ailbox 2.0 - Protokoll 0x80 - Dienste Lesen, Sc hrei ben, Speic hern, Wieder hers tell en, Pass wort @ 16\mod_1371737340053_21.doc x @ 123872 @ 3 @ 1
10.2.1
Protocol 0x80 (Parameter Access)
This protocol implements confirmed services for reading, writing, storing and
restoring of parameters.
Table 34: Protocol 0x80, Description of Services
Service
Read
Write
Save
Restore
Set password
The structure and length of the PDUs for this protocol differ for request and reply
messages.
Parameter
Protocol for reading and writing of parameters
access
Diagnostics
Protocol for transfer of diagnostics messages
Description
Reading of a parameter addressed by a table and register
number.
Writing of a parameter addressed by a table and a register
number. Written values are initially saved only to a volatile
memory. The service "Save" must be used to save parameters
to a non-volatile memory.
Save all parameters to a non-volatile memory.
Restore factory default settings. All current parameter values
will be overwritten.
You must perform this service one time before any parameters
can be written.