PROGRAMMING EXAMPLES
8.9

Program example for resetting the inverter at inverter error

The following is a program example for resetting
X0
X0F
X1 SW80.0
0
M0 X101A X20
7
Error status flag
11
REMARKS
• The above inverter reset using RY1A is available only when an inverter error occurs.
When Pr. 349 Communication reset selection = "0", inverter reset is available independently of the operation mode.
• When using the instruction code execution request (RYF) with the instruction code (HFD) and data (H9696) to reset
the inverter, set a value other than "0" in Pr. 340 Communication startup mode selection (refer to page 21) or change the
operation mode to the Network operation mode. (For the program example, refer to page 72)
• Refer to page 34 for operation conditions of inverter reset.
80
station 1
inverter at inverter error.
M0
Check the data link status of the station 1
Turn ON the error reset request flag (RY1A)
Y101A
Turn OFF the error reset request flag (RY1A)
when the error status flag (RX1A) is OFF.
END