CHAPTER 5: SETTINGS

5.7.13 Voltage elements

5.7.13.1 Menu
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  VOLTAGE ELEMENTS
 VOLTAGE ELEMENTS
These protection elements can be used for a variety of applications, such as
Undervoltage protection — For voltage sensitive loads, such as induction motors, a drop in voltage increases the
drawn current, which can cause dangerous overheating in the motor. The undervoltage protection feature can be
used to either cause a trip or generate an alarm when the voltage drops below a specified voltage setting for a
specified time delay.
Permissive functions — The undervoltage feature can be used to block the functioning of external devices by
operating an output relay when the voltage falls below the specified voltage setting. The undervoltage feature can
also be used to block the functioning of other elements through the block feature of those elements.
Source transfer schemes — In the event of an undervoltage, a transfer signal can be generated to transfer a load
from its normal source to a standby or emergency power source.
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
 PHASE
 UNDERVOLTAGE1
 PHASE
 UNDERVOLTAGE3
 PHASE
 OVERVOLTAGE1
 PHASE
 OVERVOLTAGE3
 NEUTRAL OV1
 NEUTRAL OV3
 NEG SEQ OV1
 NEG SEQ OV3
 AUXILIARY UV1
 AUXILIARY UV3
 AUXILIARY OV1
 AUXILIARY OV2
 VOLTS/HZ 1
 VOLTS/HZ 2
GROUPED ELEMENTS
See below
See page 5-285
See page 5-286
See page 5-287
See page 5-288
See page 5-289
See page 5-290