Average Values; Function Description Of Average Values; Application And Setting Notes For Average Values - Siemens 7SJ82 Manual

Siprotec 5 overcurrent protection
Table of Contents

Advertisement

Measured Values, Energy Values, and Supervision of the Primary System

10.5 Average Values

10.5
Average Values

Function Description of Average Values

10.5.1
Average values can be formed based on different measurands:
Operational measured values
Symmetrical components
Through the settings, you can set how and when the average values are formed. The settings describe:
Time slot over which the average value is formed
(Parameter: Average calc. interval )
Update interval for the display of the average values
(Parameter: Average update interval )
Synchronization time for establishing the date of commencement updating information, for example, at
the top of the hour (hh:00) or at one of the other times (hh:15, hh:30, hh:45).
(Parameter: Average synchroniz. time )
Average values are formed through the following measurands:
Operational measured values except for phase-related ratings
Amounts of the symmetrical components
You reset the average value formation via the
Binary input >Reset average value
DIGSI
The integrated operation panel
NOTE
i
i
With the P, Q sign parameter in the function block General, the sign of the following measured values
of the respective function group can be inverted (see Chapter
the Function, section Inversion of Output-Related Measured and Statistical Values):
Active power (total): P total
Reactive power (total): Q total

Application and Setting Notes for Average Values

10.5.2
The average value formation functionality is not preconfigured with the devices in the function group. If you
use the functionality, you must load it from the library into the respective function group.
The following settings listed for the calculation of the average values can be set with DIGSI and at the device.
You find the setting parameters in DIGSI in the project tree under Settings > Device settings.
Parameter: Average calc. interval
Default setting: (_:104) Average calc. interval = 60 min
Parameter Value
1 min to 60 min
Parameter: Average update interval
Default setting: (_:105) Average update interval = 60 min
1314
Description
Time slot for averaging, for example 60 minutes
10.2 Structure of the Function
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017