10.6 Minimum/Maximum Values
NOTE
i
i
With the P, Q sign parameter in the function block General, the sign of the following measured values
of the respective function group can be inverted (see Chapter
the Function, section Inversion of Output-Related Measured and Statistical Values):
Minimum/maximum values of the active and reactive power:
Min:Ptotal, Max:Ptotal, Min:Qtotal, Max:Qtotal
Minimum/maximum values of the average values of the active and reactive power:
AverageMin:Ptotal, AverageMax:Ptotal, AverageMin:Qtotal, AverageMax:Qtotal

Application and Setting Notes for Minimum/Maximum Values

10.6.2
The minimum/maximum values functionality is not preconfigured. If you want to use the functionality, you
must load it from the library into the respective function group.
The following settings listed for the calculation of the minimum/maximum values can be set with DIGSI or at
the device. You find the setting parameters in DIGSI in the project tree under Settings > Device settings.
Parameter: Min/Max cyclic reset
Default setting: (_:107) Min/Max cyclic reset = yes
Parameter Value
Yes
No
Parameter: Min/Max reset each
Default setting: (_:108) Min/Max reset each = 1 day
Parameter Value
1 day to 365 days
Parameter: Min/Max reset minute
Default setting: (_:109) Min/Max reset minute = 0 min
Parameter Value
0 min to 1439 min
Parameter: Min/Max days until start
Default setting: (_:110) Min/Max days until start = 1 day:
Parameter Value
1 day to 365 days
1318
Description
Cyclical resetting of the minimum and maximum value memories is activated
Cyclical resetting of the minimum and maximum value memories is deactivated
None of the following parameters are visible
Description
Resetting of the minimum value and the maximum value, cyclically on all specified
days, for example each day (1 day)
Description
Resetting the minimum value and the maximum value at the specified minute of the
day, which is stated in the parameter Min/Max Reset takes place every, for
example 0 min (= 00:00)
Description
Indication of when the cyclical reset procedure of the minimum values and
maximum values begins, for example in 1 day (after the parameterization)
10.2 Structure of the Function
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017