Siemens 7SJ82 Manual page 1227

Siprotec 5 overcurrent protection
Table of Contents

Advertisement

Addr.
Line drop comp.
_:15601:125
_:15601:126
_:15601:147
_:15601:127
_:15601:153
_:15601:154
_:15601:155
_:15601:156
Limiting
_:15601:102
_:15601:103
_:15601:128
_:15601:129
_:15601:148
_:15601:130
_:15601:131
_:15601:132
_:15601:149
_:15601:133
Blocking
_:15601:134
_:15601:135
_:15601:136
_:15601:150
_:15601:137
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Parameter
C
90V V.contr.3w:Line
drop compensation
90V V.contr.3w:Target
voltage rising w1
90V V.contr.3w:Target
voltage rising w2
90V V.contr.3w:Max
load current
90V V.contr.3w:R line
w1
90V V.contr.3w:X line
w1
90V V.contr.3w:R line
w2
90V V.contr.3w:X line
w2
90V V.contr.3w:Lower
tap-position limit
90V V.contr.3w:Higher
tap-position limit
90V V.contr.3w:Vmin
limiting
90V V.contr.3w:Vmin
threshold w1
90V V.contr.3w:Vmin
threshold w2
90V V.contr.3w:Vmin
time delay
90V V.contr.3w:Vmax
limiting
90V V.contr.3w:Vmax
threshold w1
90V V.contr.3w:Vmax
threshold w2
90V V.contr.3w:Vmax
time delay
90V V.contr.3w:Blocking
behavior
90V V.contr.3w:V<
Blocking
90V V.contr.3w:V<
Threshold w1
90V V.contr.3w:V<
Threshold w2
90V V.contr.3w:V< Time
delay
Setting Options
off
LDC-Z
LDC-XandR
0.0 % to 20.0 %
0.0 % to 20.0 %
0.0 % to 500.0 %
0.0 Ω to 30.0 Ω
-30.0 Ω to 30.0 Ω
0.0 Ω to 30.0 Ω
-30.0 Ω to 30.0 Ω
-128 to 127
-128 to 127
off
on
10.000 V to 340.000 V
10.000 V to 340.000 V
0 s to 20 s
off
on
10.000 V to 340.000 V
10.000 V to 340.000 V
0 s to 20 s
Auto
Auto-Manual
off
on
10.000 V to 340.000 V
10.000 V to 340.000 V
0 s to 20 s
Control Functions
8.9 Voltage Controller
Default Setting
off
4.0 %
4.0 %
100.0 %
0.0 Ω
0.0 Ω
0.0 Ω
0.0 Ω
1
15
on
105.000 V
105.000 V
10 s
on
115.000 V
115.000 V
10 s
Auto-Manual
on
90.000 V
90.000 V
0 s
1227