Application And Setting Notes; Settings; Information List - Siemens 7SJ82 Manual

Siprotec 5 overcurrent protection
Table of Contents

Advertisement

Supervision Functions
9.3 Supervision of the Secondary System
Operate delay
If it falls below the balance factor Threshold min/max and at the same time the maximum phase-to-phase
voltage exceeds the Release threshold, the Operate delay begins. If both conditions persist during
this time, the indication Failure is generated.
Blocking the Function
The following blockings reset the picked up function completely:
Externally or internally via the binary input signal
A protection pickup
The pickup signal of a protection function blocks the
9.3.5.4

Application and Setting Notes

Parameter: Threshold min/max
Recommended setting value (_:102) Threshold min/max = 0.75
The Threshold min/max parameter is used to set the ratio between the minimum (V
(V
) phase-to-phase voltage. Siemens recommends using the default setting.
max
Parameter: Release threshold
Recommended setting value (_:101) Release threshold = 50 V
With the Release threshold parameter you set the lower limit of the maximum phase-to-phase voltage
(V
). Siemens recommends using the default setting.
max
Parameter: Operate delay
Recommended setting value (_:6) Operate delay = 5.00 s
Set the Operate delay parameter so that overfunctions due to disturbing influences (such as switching
operations) are avoided. Siemens recommends using the default setting.
9.3.5.5

Settings

Addr.
Supv. balan. V
_:1
_:101
_:102
_:6
9.3.5.6

Information List

No.
Supv. balan. V
_:82
_:54
_:52
1260
Parameter
C
Supv. balan. V:Mode
Supv. balan. V:Release
threshold
Supv. balan. V:Threshold
min/max
Supv. balan. V:Delay
supervision alarm
Information
Supv. balan. V:>Block function
Supv. balan. V:Inactive
Supv. balan. V:Behavior
>Block function
Failure indication.
Setting Options
off
on
test
0.300 V to 170.000 V
0.58 to 0.95
0.00 sto 100.00 s
Data Class
(Type)
SPS
SPS
ENS
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
) and the maximum
min
Default Setting
off
50.000 V
0.75
5.00 s
Type
I
O
O