Application And Setting Notes; Settings - Siemens 7SJ82 Manual

Siprotec 5 overcurrent protection
Table of Contents

Advertisement

Blocking the Stage
In the event of blocking, the picked up stage will be reset. The following blocking options are available for the
stage:
Via the binary input signal
From inside on pickup of the Measuring-voltage failure detection function (see section
view of
Functions). The parameter Blk. by meas.-volt. failure can be set so that the meas-
uring-voltage failure detection blocks the stage or does not block it.
From an external source via the binary input signal
links in the tripping of the voltage-transformer circuit breaker. The parameter Blk. by meas.-volt.
failure can be set so that the measuring-voltage failure detection blocks the stage or does not block it.
7.7.4.2

Application and Setting Notes

Parameter: Threshold
Default setting (_:15811:3) Threshold = 0.200 p.u.
The parameter Threshold is set as a p.u. value related to the parameter Capacitor bank reference
voltage in the Capacitor bank function group.
The setting of the parameter Threshold depends on the differential voltage that occurs with the number of
defective C elements for which a warning indication or a trip command shall be generated. Determine this
differential voltage and set the Threshold slightly lower, for example, to 80 % of the value.
Parameter: Operate delay
Default setting (_:15811:6) Operate delay = 1.00 s
Set the parameter Operate delay for the specific application.
Parameter: Blk. by meas.-volt. failure
Default setting (_:15811:10) Blk. by meas.-volt. failure = yes
You can use the parameter Blk. by meas.-volt. failure to control the response of the stage when a
measuring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following 2 conditions is met:
The device-internal Measuring-voltage failure detection function is configured and switched on.
The binary input signal
the voltage-transformer circuit breaker. This binary input is available in the voltage transformers
connected to the bus voltage and capacitor-bank tap voltage. The binary input is also available in the
voltage transformer connected to the VN voltage in case of an isolated capacitor bank.
Parameter Value
no
yes
7.7.4.3

Settings

Addr.
General
_:15781:102
_:15781:101
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
>Block stage from an external or internal source.
>Open of the Voltage-transformer circuit breaker function block is connected to
Description
The stage Vdiff> is not blocked when a measuring-voltage failure is detected.
The stage Vdiff> is blocked when a measuring-voltage failure is detected.
Siemens recommends using the default setting, as correct operation of the
stage cannot be guaranteed if a measuring-voltage failure occurs.
Parameter
C
General:Matching-factor
setting
General:Voltage
matching factor
7.7 Voltage Differential Protection for Capacitors
>Open of the Volt.-transf. c. b. function block, which
Setting Options
not phase-selective
phase-selective
0.5000 to 2000.0000
Capacitor Bank Protection
9.3.2.1 Over-
Default Setting
not phase-selec-
tive
2.0000
1041