Settings - Siemens 7SJ82 Manual

Siprotec 5 overcurrent protection
Table of Contents

Advertisement

8.4.13.3

Settings

Addr.
General
_:1
_:101
_:102
_:110
_:108
_:126
De-en.gized switch.
_:105
_:106
_:107
_:103
_:104
_:109
Asynchr. op.mode
_:114
_:113
_:115
_:116
_:117
_:118
Synchr. op.mode
_:119
_:120
_:122
_:123
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Parameter
C
Syn./Asy.bal.#:Mode
Syn./Asy.bal.#:Min. oper-
ating limit Vmin
Syn./Asy.bal.#:Max.
operat. limit Vmax
Syn./
Asy.bal.#:Max.durat.
sync.process
Syn./Asy.bal.#:Direct
close command
Syn./Asy.bal.#:Voltage
adjustment
Syn./Asy.bal.#:Close
cmd. at V1< & V2>
Syn./Asy.bal.#:Close
cmd. at V1> & V2<
Syn./Asy.bal.#:Close
cmd. at V1< & V2<
Syn./Asy.bal.#:V1, V2
without voltage
Syn./Asy.bal.#:V1, V2
with voltage
Syn./Asy.bal.#:Supervi-
sion time
Syn./Asy.bal.#:Async.
operating mode
Syn./Asy.bal.#:CB make
time
Syn./Asy.bal.#:Max.
voltage diff. V2>V1
Syn./Asy.bal.#:Max.
voltage diff. V2<V1
Syn./Asy.bal.#:Max.
frequency diff. f2>f1
Syn./Asy.bal.#:Max.
frequency diff. f2<f1
Syn./Asy.bal.#:Sync.
operating mode
Syn./Asy.bal.#:f-
threshold ASYN<->SYN
Syn./Asy.bal.#:Max.
voltage diff. V2>V1
Syn./Asy.bal.#:Max.
voltage diff. V2<V1
8.4 Synchronization Function
Setting Options
off
on
test
0.300 V to 340.000 V
0.300 V to 340.000 V
0.00 s to 3600.00 s; ∞
no
yes
0.500 to 2.000
no
yes
no
yes
no
yes
0.300 V to 170.000 V
0.300 V to 340.000 V
0.00 s to 60.00 s
off
on
0.01 s to 0.60 s
0.000 V to 170.000 V
0.000 V to 170.000 V
0.000 Hz to 4.000 Hz
0.000 Hz to 4.000 Hz
off
on
0.010 Hz to 0.200 Hz
0.000 V to 170.000 V
0.000 V to 170.000 V
Control Functions
Default Setting
off
90.000 V
110.000 V
30.00 s
no
1.000
no
no
no
5.000 V
80.000 V
0.10 s
off
0.06 s
2.000 V
2.000 V
0.100 Hz
0.100 Hz
off
0.010 Hz
2.000 V
2.000 V
1163

Advertisement

Table of Contents
loading

This manual is also suitable for:

7sj85

Table of Contents