Siemens 7SJ82 Manual page 1224

Siprotec 5 overcurrent protection
Table of Contents

Advertisement

Control Functions
8.9 Voltage Controller
Addr.
_:14011:124
_:14011:155
_:14011:160
Line drop comp.
_:14011:125
_:14011:126
_:14011:127
_:14011:153
_:14011:154
Limiting
_:14011:102
_:14011:103
_:14011:128
_:14011:129
_:14011:130
_:14011:131
_:14011:132
_:14011:133
Blocking
_:14011:134
_:14011:135
_:14011:136
_:14011:137
_:14011:138
_:14011:139
_:14011:140
_:14011:141
1224
Parameter
C
90V V.contr.2w:Function
monitoring
90V V.contr.2w:Regulate
with T2 at start
90V V.contr.2w:Set
point mode active
90V V.contr.2w:Line
drop compensation
90V V.contr.2w:Target
voltage rising
90V V.contr.2w:Max
load current
90V V.contr.2w:R line
90V V.contr.2w:X line
90V V.contr.2w:Lower
tap-position limit
90V V.contr.2w:Higher
tap-position limit
90V V.contr.2w:Vmin
limiting
90V V.contr.2w:Vmin
threshold
90V V.contr.2w:Vmin
time delay
90V V.contr.2w:Vmax
limiting
90V V.contr.2w:Vmax
threshold
90V V.contr.2w:Vmax
time delay
90V V.contr.2w:Blocking
behavior
90V V.contr.2w:V<
Blocking
90V V.contr.2w:V<
Threshold
90V V.contr.2w:V< Time
delay
90V V.contr.2w:I>
Blocking
90V V.contr.2w:I>
Threshold
90V V.contr.2w:I> Time
delay
90V V.contr.2w:I<
Blocking
Setting Options
0 min to 120 min
off
on
off
on
off
LDC-Z
LDC-XandR
0.0 % to 20.0 %
0.0 % to 500.0 %
0.0 Ω to 30.0 Ω
-30.0 Ω to 30.0 Ω
-128 to 127
-128 to 127
off
on
10.000 V to 340.000 V
0 s to 20 s
off
on
10.000 V to 340.000 V
0 s to 20 s
Auto
Auto-Manual
off
on
10.000 V to 340.000 V
0 s to 20 s
off
on
10 % to 500 %
0 s to 20 s
off
on
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Default Setting
15 min
on
on
off
4.0 %
100.0 %
0.0 Ω
0.0 Ω
1
15
on
105.000 V
10 s
on
115.000 V
10 s
Auto-Manual
on
90.000 V
0 s
on
150 %
0 s
off

Advertisement

Table of Contents
loading

This manual is also suitable for:

7sj85

Table of Contents