2.5
Selecting Data Clear Processing for Communications
Error
Use function code y95
If the inverter causes an alarm due to a communications error* (including a bus link error), it can
zero-clear communication commands stored in the memory as specified by y95.
Data for y95
0
Do not clear the data of function codes Sxx when a communications error occurs.
(compatible with the conventional inverters)
1
Clear the data of function codes S01, S05 and S19 when a communications error
occurs.
2
Clear the run command-assigned bit of function code S06 when a communications
error occurs.
Clear both data of S01, S05 and S19 and run command-assigned bit of S06 when a
3
communications error occurs.

2.5 Selecting Data Clear Processing for Communications Error

*Object errors: Er8, ErP, Er4, Er5 and ErU
Function
2-23